Model | JGFH-125JS |
Rated Current Range | 32–125A (JGFH-125JS) 100–250A (JGFH-250JS) 160–400A (JGFH-400JS) |
Protection Functions | Overvoltage, Undervoltage, Overcurrent, Leakage, Phase Loss, Neutral Loss |
Protection Settings Range | Overvoltage: 210–300V (default 265V) Undervoltage: 120–200V (default 170V) Residual Current: 1–1000mA (default 75mA) Overcurrent: 32–125A (for 125 model) Three-phase Unbalance: Default Off (P000) |
Response Time | Power-On Delay: 20s Fault Disconnection: ≤3s 1× Current Trip Time: 1–120s (Default 5s) 1.1× Current Trip Time: <0.1s Voltage Protection Action Time: 0.1–10s (Default 0.1s) Leakage Action Time: <0.1s |
Communication Protocol | Supports standard Modbus485 |
Operating Temperature | -5℃ to +40℃ (24h average ≤ +35℃) |